Factory-Trained Technicians
ISO-compliant process
Allen-Bradley PowerFlex 700 20BD180A3AYNARB0 | 150 kW / 180 A VFD
Get it Repaired or Get a Replacement Today
If your PowerFlex 700 fails or throws random faults, Flexa Systems can repair your 20BD180A3AYNARB0 in-house at the component level or ship you a fully tested replacement unit from our stocked inventory.
Key Specifications
- Input Voltage: 480V AC
- Current (Amps): 180
- Power Rating: 150 kW / 201 HP
- Frame: 6
- Enclosure: IP20, NEMA/UL Type 1
- HMI Presence: LCD Display, Full Numeric Keypad
- Documentation: Manual
- Brake: Yes
- Internal Braking Resistor: No
- Emission: CE Filter: Yes, CM Choke: Yes
- Comm Slot: N/A
- Control & I/O: Standard | 115V AC
- Feedback: None
Most Common Faults We Can Solve
These are frequent PowerFlex 700 issues. We diagnose quickly and repair at the component level.
- Cntl Bd Overtemp: Main Control Board over-temperature.
Fix: Check board fan and ambient; we replace fans and re-flow/replace the MCB if required.
- SW OverCurrent: 1 ms current exceeded its rating (above cont., below HW limit).
Fix: Reduce load/boost/brake volts; we capture waveforms and reset to safe values.
- OverVoltage: DC bus voltage exceeded the maximum value.
Fix: Verify line transients; extend decel time or add a dynamic brake option; we can size/install a DB kit and soak-test the drive.
- Encoder Quad Err: Both channels changed in one clock (noise or fault).
Fix: Reduce noise/replace encoder; we tidy shielding/grounds and retest.
- Heatsink OverTemp: Heatsink temperature above limit (or very low).
Fix: Verify ambient, fan operation, and load; we replace fans and clean/recertify cooling path.
- UnderVoltage: DC bus dropped below the minimum threshold.
Fix: Check incoming AC for sags/interruption; we test input and DC bus health and stabilize with line conditioning if needed.
- OverSpeed Limit: Speed correction exceeded [Overspeed Limit].
Fix: Remove overhauling load or raise limit; we re-tune slip/bus regulation.
Important Notes
Pricing listed on the website is for reference only and is subject to change over time.
Send us your full catalog number (or a photo) and Flexa Systems will verify compatibility before you order.
We keep you running with repair or replacement for Allen-Bradley PowerFlex 700 drives—whichever gets you back online faster.
- Units are inspected, repaired as needed, and load-tested.
- Lead time and pricing depend on condition and availability.
- Exchange and hot-rush options offered on request.