Key Specifications
- Input Voltage: 480V AC
- Current (Amps): 180
- Power Rating: 150 kW / 201 HP
- Frame: 6
- Enclosure: IP20, NEMA/UL Type 1
- HMI Presence: LCD Display, Full Numeric Keypad
- Documentation: Manual
- Brake: Yes
- Internal Braking Resistor: No
- Emission: CE Filter: Yes, CM Choke: Yes
- Comm Slot: None
- Control & I/O: Vector | 24V DC
- Feedback: Encoder, 12V/5V
Most Common Faults We Can Solve
These are frequent PowerFlex 700 issues. We diagnose quickly and repair at the component level.
- UnderVoltage: DC bus dropped below the minimum threshold.
Fix: Check incoming AC for sags/interruption; we test input and DC bus health and stabilize with line conditioning if needed.
- SW OverCurrent: 1 ms current exceeded its rating (above cont., below HW limit).
Fix: Reduce load/boost/brake volts; we capture waveforms and reset to safe values.
- Drive OverLoad: 110% for 1 min or 150% for 3 s exceeded.
Fix: Reduce load or increase accel time; we profile current vs. cycle and tune ramps.
- Encoder Quad Err: Both channels changed in one clock (noise or fault).
Fix: Reduce noise/replace encoder; we tidy shielding/grounds and retest.
- Ground Fault: >25% rating current to earth ground detected.
Fix: Meg-check motor and cable for ground; we isolate insulation faults and re-terminate.
- Input Phase Loss: Ripple indicates a missing input phase or blown fuse.
Fix: Inspect fuses and incoming power; we verify phase balance and replace protection if necessary.
- Output Phase Loss: Current lost in one/more output phases.
Fix: Check motor/drive wiring; we test phase continuity and repair output stage/wiring faults.
Important Notes
Pricing listed on the website is for reference only and is subject to change over time.
Unsure about the exact model? Share a photo or full catalog code. Flexa Systems will confirm compatibility fast.
We service and stock Allen-Bradley PowerFlex 700 VFDs—component-level repairs or ready-to-ship replacements.
- Load testing is performed on all units prior to shipment.
- Lead times and pricing depend on condition and options.
- Expedited exchange programs available.
- 12–24 month coverage on repairs and remans (where applicable).
Same-Day Quote • Repair or Exchange
We repair, test, and ship quickly — or provide a ready-to-ship replacement when available.
Request Service/Quote
Serving all 50 states from Texas. Rush options available.