Fast Turnaround & Testing
Phone support by engineers
Allen-Bradley PowerFlex 700 20BD096F3ANNANC0 | 75 kW / 96 A VFD
Bench Repair or Advanced Exchange Program
If your PowerFlex 700 fails or throws random faults, Flexa Systems can repair your 20BD096F3ANNANC0 in-house at the component level or ship you a fully tested replacement unit from our stocked inventory.
Key Specifications
- Input Voltage: 480V AC
- Current (Amps): 96
- Power Rating: 75 kW / 101 HP
- Frame: 5
- Enclosure: Open/Flange Mount – Front: IP00, NEMA/UL Type Open; Back/Heatsink: IP54, NEMA 12
- HMI Presence: LCD Display, Full Numeric Keypad
- Documentation: Manual
- Brake: No
- Internal Braking Resistor: No
- Emission: CE Filter: Yes, CM Choke: Yes
- Comm Slot: None
- Control & I/O: Vector | 24V DC
- Feedback: None
Most Common Faults We Can Solve
These are frequent PowerFlex 700 issues. We diagnose quickly and repair at the component level.
- Power Loss: DC bus <85% of nominal longer than [Power Loss Time].
Fix: Monitor AC for dips; we add ride-through measures as needed.
- Heatsink OverTemp: Heatsink temperature above limit (or very low).
Fix: Verify ambient, fan operation, and load; we replace fans and clean/recertify cooling path.
- Decel Inhibit: Bus regulation halts decel to limit DC bus.
Fix: Verify line & grounding, add DB resistor or lengthen decel; we configure/supply DB.
- Encoder Loss: One encoder channel missing (requires differential).
Fix: Verify wiring, rotation, pulse rate; we replace encoder/cable and re-align.
- UnderVoltage: DC bus dropped below the minimum threshold.
Fix: Check incoming AC for sags/interruption; we test input and DC bus health and stabilize with line conditioning if needed.
- SW OverCurrent: 1 ms current exceeded its rating (above cont., below HW limit).
Fix: Reduce load/boost/brake volts; we capture waveforms and reset to safe values.
- Load Loss: Torque current below [Load Loss Level] for set time.
Fix: Verify mechanical coupling; we check level/time and drive feedback.
Important Notes
Pricing listed on the website is for reference only and is subject to change over time.
Unsure about the exact model? Share a photo or full catalog code. Flexa Systems will confirm compatibility fast.
We service and stock Allen-Bradley PowerFlex 700 VFDs—component-level repairs or ready-to-ship replacements.
- Load testing is performed on all units prior to shipment.
- Lead times and pricing depend on condition and options.
- Expedited exchange programs available.
- 12–24 month coverage on repairs and remans (where applicable).
Speak to a Technician
Send a part number or quick video of the fault. We’ll guide next steps immediately.
Talk to a Tech
No-fix, no-fee on repairs. Honest diagnostics, fast turnaround.