Rush Service Available
Same-day evaluation
Allen-Bradley PowerFlex 700 20BD022A3AYNANC1 | 15 kW / 22 A VFD
Repair Estimate or Ship Confirmed
If your PowerFlex 700 fails or throws random faults, Flexa Systems can repair your 20BD022A3AYNANC1 in-house at the component level or ship you a fully tested replacement unit from our stocked inventory.
Key Specifications
- Input Voltage: 480V AC
- Current (Amps): 22
- Power Rating: 15 kW / 20 HP
- Frame: 1
- Enclosure: IP20, NEMA/UL Type 1
- HMI Presence: LCD Display, Full Numeric Keypad
- Documentation: Manual
- Brake: Yes
- Internal Braking Resistor: No
- Emission: CE Filter: Yes, CM Choke: Yes
- Comm Slot: None
- Control & I/O: Vector | 24V DC
- Feedback: Encoder, 12V/5V
Most Common Faults We Can Solve
These are frequent PowerFlex 700 issues. We diagnose quickly and repair at the component level.
- Transistor OverTemp: Power devices exceeded safe temperature.
Fix: Same as above—cooling & load audit; we replace failed fans/IGBTs and test.
- Heatsink OverTemp: Heatsink temperature above limit (or very low).
Fix: Verify ambient, fan operation, and load; we replace fans and clean/recertify cooling path.
- HW OverCurrent: Output current exceeded hardware limit.
Fix: Check programming & load; we review boost/DC brake settings and load profile.
- OverVoltage: DC bus voltage exceeded the maximum value.
Fix: Verify line transients; extend decel time or add a dynamic brake option; we can size/install a DB kit and soak-test the drive.
- SW OverCurrent: 1 ms current exceeded its rating (above cont., below HW limit).
Fix: Reduce load/boost/brake volts; we capture waveforms and reset to safe values.
- Phase UV/VW/UW Short: Excessive current between output terminals.
Fix: Check for shorted motor/wiring; we repair/replace damaged output stage.
- Output Phase Loss: Current lost in one/more output phases.
Fix: Check motor/drive wiring; we test phase continuity and repair output stage/wiring faults.
Important Notes
Pricing listed on the website is for reference only and is subject to change over time.
Unsure about the exact model? Share a photo or full catalog code. Flexa Systems will confirm compatibility fast.
We service and stock Allen-Bradley PowerFlex 700 VFDs—component-level repairs or ready-to-ship replacements.
- Load testing is performed on all units prior to shipment.
- Lead times and pricing depend on condition and options.
- Expedited exchange programs available.
- 12–24 month coverage on repairs and remans (where applicable).
Speak to a Technician
Send a part number or quick video of the fault. We’ll guide next steps immediately.
Talk to a Tech
No-fix, no-fee on repairs. Honest diagnostics, fast turnaround.