Drive Specialists Since 2012
Free failure analysis
Allen-Bradley PowerFlex 700 20BD014A0AYNADD0 | 10 kW / 14 A VFD
Diagnose & Repair or Next-Day Replacement
If your PowerFlex 700 fails or throws random faults, Flexa Systems can repair your 20BD014A0AYNADD0 in-house at the component level or ship you a fully tested replacement unit from our stocked inventory.
Key Specifications
- Input Voltage: 480V AC
- Current (Amps): 14
- Power Rating: 10 kW / 13 HP
- Frame: 1
- Enclosure: IP20, NEMA/UL Type 1
- HMI Presence: Blank Cover
- Documentation: Manual
- Brake: Yes
- Internal Braking Resistor: No
- Emission: CE Filter: Yes, CM Choke: Yes
- Comm Slot: DeviceNet
- Control & I/O: Vector | 115V AC
- Feedback: None
Most Common Faults We Can Solve
These are frequent PowerFlex 700 issues. We diagnose quickly and repair at the component level.
- Ground Fault: >25% rating current to earth ground detected.
Fix: Meg-check motor and cable for ground; we isolate insulation faults and re-terminate.
- Encoder Loss: One encoder channel missing (requires differential).
Fix: Verify wiring, rotation, pulse rate; we replace encoder/cable and re-align.
- SW OverCurrent: 1 ms current exceeded its rating (above cont., below HW limit).
Fix: Reduce load/boost/brake volts; we capture waveforms and reset to safe values.
- Input Phase Loss: Ripple indicates a missing input phase or blown fuse.
Fix: Inspect fuses and incoming power; we verify phase balance and replace protection if necessary.
- HW OverCurrent: Output current exceeded hardware limit.
Fix: Check programming & load; we review boost/DC brake settings and load profile.
- Encoder Quad Err: Both channels changed in one clock (noise or fault).
Fix: Reduce noise/replace encoder; we tidy shielding/grounds and retest.
- UnderVoltage: DC bus dropped below the minimum threshold.
Fix: Check incoming AC for sags/interruption; we test input and DC bus health and stabilize with line conditioning if needed.
Important Notes
Pricing listed on the website is for reference only and is subject to change over time.
Unsure about the exact model? Share a photo or full catalog code. Flexa Systems will confirm compatibility fast.
We service and stock Allen-Bradley PowerFlex 700 VFDs—component-level repairs or ready-to-ship replacements.
- Load testing is performed on all units prior to shipment.
- Lead times and pricing depend on condition and options.
- Expedited exchange programs available.
- 12–24 month coverage on repairs and remans (where applicable).
Repair & Sales • PowerFlex Specialists
Component-level repairs, reman units, and ready-to-ship replacements when available.
Check Availability
Send your requirement — we’ll match repair or stock options.